ABB Brand AX25-30-01-81 24V 50/60Hz Contactor

0.00

ABB Brand contactors are mainly used for controlling 3-phase motors and power circuits up to 690 V AC. These contactors are of the block type design with: – 3 main poles and 1 built-in auxiliary contact – control circuit: AC operated – add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.

Description

Max Mechanical Switching Frequency 3600 cycles per hour
Max Electrical Switching Frequency AC-1 600 cycles per hour, AC-15 1200 cycles per hour, AC-3 1200 cycles per hour, DC-13 900 cycles per hour
Horsepower Rating UL/CSA (120 V AC) Single Phase 2 horsepower, (240 V AC) Single Phase 3 horsepower, (200 … 208 V AC) Three Phase 7.5 horsepower, (220 … 240 V AC) Three Phase 7.5 horsepower, (440 … 480 V AC) Three Phase 15 horsepower, (550 … 600 V AC) Three Phase 15 horse
Conventional Free-air Thermal Current (Ith) acc. to IEC 60947-4-1, Open Contactors q = 40 °C 32 ampere, acc. to IEC 60947-5-1, q = 40 °C 16 ampere
Terminal Type Screw Terminals
Rated Operational Voltage Auxiliary Circuit 690 volt, Main Circuit 690 volt
Operate Time Between Coil De-energization and NC Contact Closing 9 … 16 millisecond, Between Coil De-energization and NO Contact Opening 4 … 11 millisecond, Between Coil Energization and NC Contact Opening 7 … 21 millisecond, Between Coil Energization and NO Con
Rated Control Circuit Voltage (Uc) 50 Hz 24V; 60 Hz 24V
Rated Operational Power AC-3 (Pe) (220 / 230 / 240 V) 6.5 kilowatt, (380 / 400 V) 11 kilowatt, (415 V) 11 kilowatt, (440 V) 9 kilowatt, (500 V) 9 kilowatt, (690 V) 9 kilowatt
Rated Operational Current DC-13 (Ie) (110 V) 1.1 A / 121 watt, (220 V) 0.55 A / 121 watt, (400 V) 2.8 A / 134 watt, (500 V) 2 A / 144 watt, (125 V) 1.1 A / 138 watt, (24 V) 6 A / 144 watt, (250 V) 0.55 A / 138 watt
Rated Operational Current AC-3 (Ie) (220 / 230 / 240 V) 55 °C 25 ampere, (380 / 400 V) 55 °C 25 ampere, (415 V) 55 °C 25 ampere, (440 V) 55 °C 16 ampere, (500 V) 55 °C 14 ampere, (690 V) 55 °C 10 ampere
Rated Operational Current AC-15 (Ie) (220 / 240 V) 4 ampere, (24 / 127 V) 6 ampere, (400 / 440 V) 2 ampere, (500 V) 2 ampere, (690 V) 2 ampere, (380 / 440 V) 3 ampere
Rated Operational Current AC-1 (Ie) (690 V) 40 °C 32 ampere, (690 V) 70 °C 23 ampere, (220 / 240 V) 55 °C 27 ampere
Rated Frequency (f) Auxiliary Circuit 50 / 60 hertz, Main Circuit 50 / 60 hertz
Rated Short-time Withstand Current (Icw) at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 200 ampere, at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 32 ampere, at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 85 ampere, at 40 °C Ambient Temp, in Free Air, from
Package Width 48 millimetre
Package Length 78 millimetre
Package Height 79 millimetre
Invoice Description AX25-30-01-81 24V 50/60Hz Contactor
Product Range AX25
Package Gross Weight 0.34 kilogram
Extended Product Type AX25-30-01-81
Number of Aux Contacts NC 1
General Use Rating UL/CSA (600 V AC) 30 ampere
Full Load Amps Motor Use (120 V AC) Single Phase 24 ampere, (240 V AC) Single Phase 17 ampere, (200 … 208 V AC) Three Phase 25.3 ampere, (220 … 240 V AC) Three Phase 22 ampere, (440 … 480 V AC) Three Phase 21 ampere, (550 … 600 V AC) Three Phase 17 ampere
Ambient Air Temperature Close to Contactor for Storage -60 … +80 degree Celsius, Close to Contactor Fitted with Thermal O/L Relay -25 … +55 degree Celsius, Close to Contactor without Thermal O/L Relay -40 … +70 degree Celsius, Near Contactor for Operation in Free Air -40 .
Rated Insulation Voltage (Ui) acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 volt