Technical Specification | Details |
---|---|
Number of Poles | 3P |
Mini Contactor Type | Mini Contactor |
Rated Operational Voltage | Auxiliary Circuit 690 V AC Auxiliary Circuit 250 V DC Main Circuit 690 V AC Main Circuit 220 V DC |
Rated Frequency (f) | Control Circuit 400 Hz Control Circuit 50 Hz Control Circuit 60 Hz Main Circuit 50 Hz Main Circuit 60 Hz Main Circuit DC |
Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV Main Circuit 6 kV |
Rated Insulation Voltage (Ui) | 690 V acc. to UL/CSA 600 V |
Number of Main Contacts NC | 0 |
Number of Main Contacts NO | 3 |
Rated Operational Current AC-1 (Ie) | (220 / 240 V) 40 °C 20 A (220 / 240 V) 55 °C 16 A (380 / 440 V) 40 °C 20 A (380 / 440 V) 55 °C 16 A (690 V) 40 °C 6 A (690 V) 55 °C 6 A |
Rated Operational Power AC-3 (Pe) | (230 V) Three Phase 2.2 kW (400 V) Three Phase 4 kW (500 V) Three Phase 4 kW (690 V) Three Phase, NO 3 kW |
Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A |
Number of Auxiliary Contacts NC | 1 |
Number of Auxiliary Contacts NO | 0 |
Rated Operational Current AC-15 (Ie) | (24 V) 4 A (120 V) 4 A (500 V) 2 A (220 / 240 V) 4 A (380 / 400 V) 3 A |
Rated Operational Current DC-13 (Ie) | (24 V) 2.5 A (110 V) 0.7 A (220 / 240 V) 0.4 A |
Conventional Free-air Thermal Current (Ith) | Main Circuit 20 A |
Rated Control Circuit Voltage (Uc) | 24 V AC |
Coil Operating Limits | (acc. to IEC 60947-4-1) for AC supply 0.85 … 1.1 x Uc (at θ ≤ 55 °C) |
Degree of Protection | Auxiliary Circuit Terminals IP20 Control Circuit Terminals IP20 Main Circuit Terminals IP20 |
Mechanical Durability | 10000000 cycles |
Minimum Switching Capacity | Auxiliary Circuit 17 V Auxiliary Circuit 5 mA |
Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour (AC-15) 600 cycles per hour (AC-3) 600 cycles per hour (DC-1) 600 cycles per hour (DC-13) 600 cycles per hour (DC-3) 600 cycles per hour |
Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 1 … 2.5 mm² Flexible with Insulated Ferrule 1/2x 1 … 2.5 mm² Flexible 1/2x 1 … 2.5 mm² Rigid 1/2x 1 … 4 mm² |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 1 … 2.5 mm² Flexible with Insulated Ferrule 1/2x 1 … 2.5 mm² Flexible 1/2x 1 … 2.5 mm² Rigid 1/2x 1 … 4 mm² |
Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 1 … 2.5 mm² Flexible with Insulated Ferrule 1/2x 1 … 2.5 mm² Flexible 1/2x 1 … 2.5 mm² Rigid 1/2x 1 … 4 mm² |
Wire Stripping Length | Auxiliary Circuit 9 mm Control Circuit 9 mm Main Circuit 9 mm |
Tightening Torque | Auxiliary Circuit 0.8 … 1.1 N·m Control Circuit 0.8 … 1.1 N·m Main Circuit 0.8 … 1.1 N·m |
Recommended Screw Driver | M3, Pozidriv 1 |