Contact | 94426-33195
Email: info@shansen.in

ABB Brand NX22E-86 400-415V50Hz/415V-440V60Hz Contactor Relay

0.00

NX…contactor relays are used for switching auxiliary circuits and control circuits. These contactor relays are of the block type design with: – 4 poles. Contactor relays have mechanically linked auxiliary contact elements – control circuit: AC operated – add-on auxiliary contact blocks for front or side mounting and a wide range of accessories.

Description

  • Product Net Width:
    44 mm
  • Product Net Depth / Length:
    74 mm
  • Product Net Height:
    74 mm
  • Product Net Weight:
    0.315 kg

Technical

  • Number of Auxiliary Contacts NO:
    2
  • Number of Auxiliary Contacts NC:
    2
  • Rated Operational Voltage:
    Auxiliary Circuit 690 V
    Main Circuit 690 V
  • Rated Frequency (f):
    Auxiliary Circuit 50 / 60 Hz
    Main Circuit 50 / 60 Hz
  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-5-1, q = 40 °C 16 A
  • Rated Operational Current AC-15 (Ie):
    (220 / 240 V) 4 A
    (24 / 127 V) 6 A
    (400 / 440 V) 2 A
    (500 V) 2 A
    (690 V) 2 A
    (380 / 440 V) 3 A
  • Rated Short-time Withstand Current (Icw):
    for 0.1 s 140 A
    for 1 s 100 A
  • Maximum Electrical Switching Frequency:
    (AC-15) 1200 cycles per hour
    (DC-13) 900 cycles per hour
  • Rated Operational Current DC-13 (Ie):
    (110 V) 0.55 A / 60 W
    (220 V) 0.30 A / 66 W
    (400 V) 2.8 A / 134 W
    (500 V) 1 A / 72 W
    (125 V) 0.55 A / 69 W
    (24 V) 6 A / 144 W
    (250 V) 0.30 A / 75 W
  • Rated Insulation Voltage (Ui):
    acc. to IEC 60947-5-1 and VDE 0110 (Gr. C) 690 V
  • Rated Impulse Withstand Voltage (Uimp):
    6 kV
  • Maximum Mechanical Switching Frequency:
    6000 cycles per hour
  • Rated Control Circuit Voltage (Uc):
    50 Hz 400 … 415 V
    60 Hz 415 … 440 V
  • Operate Time:
    Between Coil De-energization and NC Contact Closing 9 … 16 ms
    Between Coil De-energization and NO Contact Opening 4 … 11 ms
    Between Coil Energization and NC Contact Opening 7 … 21 ms
    Between Coil Energization and NO Contact Closing 10 … 26 ms
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
  • Terminal Type:
    Screw Terminals

Technical UL/CSA

  • Tightening Torque UL/CSA:
    Auxiliary Circuit 9 in·lb
    Control Circuit 9 in·lb

Environmental

  • Ambient Air Temperature:
    Close to Contactor for Storage -60 … +80 °C
    Close to Contactor Fitted with Thermal O/L Relay -25 … +55 °C
    Close to Contactor without Thermal O/L Relay -40 … +70 °C
    Near Contactor for Operation in Free Air -40 … +70 °C
  • Climatic Withstand:
    acc. to IEC 60068-2-30 and 60068-2-11 – UTE C 63-100 specification II
  • RoHS Status:
    Following EU Directive 2002/95/EC August 18, 2005 and amendment
    Maximum Operating Altitude Permissible:
    3000 m

Additional information

Brand

ABB

Type

Contactor Relay