WhatsApp | 94426-33195
Email: info@shansen.in

ABB Make A9-22-00 24V50Hz / 24V60Hz Contactor

0.00

Meet the ABB Brand A9-22-00 Contactor, your reliable partner for managing non-inductive or slightly inductive loads. This versatile 4-pole contactor is perfect for a range of applications, from resistance furnaces to lighting systems. Engineered to handle power circuits up to 690 V AC and 440 V DC, it combines robust performance with exceptional reliability.

Key Features

Versatile Application: Ideal for controlling non-inductive or slightly inductive loads like resistance furnaces. It’s also great for general power circuit control and lighting applications.

Design Excellence: The A series 4-pole contactors feature a block type design, ensuring durability and ease of use.

Flexible Contact Blocks: Equipped with 2 N.O. (Normally Open) and 2 N.C. (Normally Closed) main poles, along with front and side-mounted add-on auxiliary contact blocks, it offers unparalleled flexibility.

Reliable Control Circuit: The AC-operated control circuit with a laminated magnet circuit guarantees dependable operation.

Wide Range of Accessories: Customize your setup with a variety of available accessories to meet your specific needs.

Where to Buy

Looking to get your hands on the ABB Brand A9-22-00 Contactor? Shansen Enterprises in Coimbatore is your authorized dealer. Renowned for their quality and reliability, Shansen Enterprises supplies ABB contactors, relays, and circuit breakers throughout Coimbatore and across India. For all your contactor needs, they’ve got you covered!

FAQs

1. What type of loads is the A9-22-00 Contactor suitable for?

The A9-22-00 Contactor is designed for controlling non-inductive or slightly inductive loads, such as resistance furnaces. It’s also suitable for general power circuits and lighting applications.

2. What are the main features of this contactor?

Key features include a block type design, 2 N.O. and 2 N.C. main poles, front and side-mounted add-on auxiliary contact blocks, an AC-operated control circuit with a laminated magnet circuit, and a wide range of accessories.

3. What voltage can this contactor handle?

The A9-22-00 Contactor can handle power circuits up to 690 V AC and 440 V DC.

4. Where can I purchase the ABB Brand A9-22-00 Contactor?

You can purchase the A9-22-00 Contactor from Shansen Enterprises, an authorized dealer located in Coimbatore. They supply ABB contactors, relays, and circuit breakers across Coimbatore and throughout India.

Description

Dimensions

  • Product Net Width:
    44 mm
  • Product Net Depth / Length:
    74 mm
  • Product Net Height:
    74 mm
  • Product Net Weight:
    0.34 kg

Technical

  • Number of Main Contacts NO:
    2
  • Number of Main Contacts NC:
    2
  • Number of Auxiliary Contacts NO:
    0
  • Number of Auxiliary Contacts NC:
    0
  • Standards:
    Devices complying with international standards IEC 947-1 / 947-4-1, and European standards EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) acc. to amendment A11 to IEC 947-1, EN 60 947-1 and amendment 2 to IEC 947-4-1
  • Rated Operational Voltage:
    Main Circuit 690 V
  • Conventional Free-air Thermal Current (Ith):
    acc. to IEC 60947-4-1, Open Contactors q = 40 °C 26 A
  • Rated Operational Current AC-1 (Ie):
    (690 V) 40 °C 25
    (690 V) 55 °C 22
    (690 V) 70 °C 18
  • Rated Operational Current AC-3 (Ie):
    (220 / 230 / 240 V) 55 °C 9 A
    (380 / 400 V) 55 °C 9 A
    (415 V) 55 °C 9 A
    (440 V) 55 °C 9 A
    (500 V) 55 °C 9 A
    (690 V) 55 °C 7 A
  • Rated Breaking Capacity AC-3 acc. to IEC 60947-4-1:
    8 x Ie AC-3
  • Rated Making Capacity AC-3 acc. to IEC 60947-4-1:
    10 x Ie AC-3
  • Short-Circuit Protective Devices:
    gG Type Fuses 25 A
  • Maximum Breaking Capacity:
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
    cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
  • Maximum Electrical Switching Frequency:
    (AC-1) 600 cycles per hour
    (AC-2 / AC-4) 300 cycles per hour
    (AC-3) 1200 cycles per hour
  • Rated Insulation Voltage (Ui):
    acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
    acc. to UL/CSA 600 V
  • Rated Impulse Withstand Voltage (Uimp):
    8 kV
  • Mechanical Durability:
    10 million
  • Maximum Mechanical Switching Frequency:
    3600 cycles per hour
  • Rated Control Circuit Voltage (Uc):
    50 Hz 24 V
    60 Hz 24 V
  • Coil Consumption:
    Average Holding Value 50 / 60 Hz 8 2 V·A
    Average Pull-in Value 50 Hz 74 V·A
    Average Pull-in Value 60 Hz 70 V·A
    Holding at Max. Rated Control Circuit Voltage 50 Hz 8 2 V·A
    Holding at Max. Rated Control Circuit Voltage 60 Hz 8 2 V·A
    Pull-in at Max. Rated Control Circuit Voltage 50 Hz 74 V·A
    Pull-in at Max. Rated Control Circuit Voltage 60 Hz 70 V·A
  • Operate Time:
    Between Coil De-energization and NC Contact Closing 9 … 16 ms
    Between Coil De-energization and NO Contact Opening 4 … 11 ms
    Between Coil Energization and NC Contact Opening 7 … 21 ms
    Between Coil Energization and NO Contact Closing 10 … 26 ms
  • Connecting Capacity Main Circuit:
    Flexible with Cable End 0.75 … 2.5 mm²
    Rigid Cable 1 … 4 mm²
  • Connecting Capacity Auxiliary Circuit:
    Flexible with Cable End 0.75 … 2.5 mm²
    Rigid Cable 1 … 4 mm²
  • Degree of Protection:
    acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
  • Connecting Terminals (delivered in open position) Main Poles:
    M 3.5 (+,-) pozidriv 2 screw with cable clamp
  • Terminal Type:
    Screw Terminals

Environmental

  • Ambient Air Temperature:
    Close to Contactor for Storage -60 … +80 °C
    Near Contactor for Operation in Free Air (0.85 … 1.1 Uc) -40 … +55 °C
    Near Contactor for Operation in Free Air (Uc) -40 … +70 °C
  • Climatic Withstand:
    acc. to IEC 60068-2-30 and 60068-2-11 – UTE C 63-100 specification II
  • Maximum Operating Altitude Permissible:
    3000 m
  • Resistance to Shock acc. to IEC 60068-2-27:
    Closed, Shock Direction: B1 10 K40
    Open, Shock Direction: B1 5 K40
    Shock Direction: A 20 K40
    Shock Direction: B2 15 K40
    Shock Direction: C1 20 K40
    Shock Direction: C2 20 K40
  • RoHS Status:
    Following EU Directive 2011/65/EU

Additional information

Brand

ABB

Type

Contactor