Description

₹0.00
Upgrade your electrical protection with the Eaton PLSI-C25/3-GI triple-pole MCB. Engineered for reliability, it offers high breaking capacity in a slim DIN-rail design. Perfectly balanced between global standards and local demands, this C-curve breaker safeguards circuits in homes, offices, and light-industrial setups. Built to last with robust materials and silver-alloy contacts, it ensures fast fault clearance and clear status indication. Ready for seamless installation and years of trouble-free operation.
Key Features at a Glance
Triple-pole (3P), 25 A, C-curve MCB
10 kA breaking capacity (Icu) / 7.5 kA service breaking (Ics)
Rated for 240/415 V AC, 50 Hz
Silver-alloy contacts + 13-plate DeNiro arc-chutes
True contact indicator (red/green)
Fire-retardant, IP20 housing
Quick-break, trip-free mechanism
DIN-rail 35 mm mounting, M5 combi-head terminals
Why Choose This Product
The Eaton PLSI-C25/3-GI combines global IEC compliance with “Made for India” durability—ideal for challenging power environments. Its high 10 kA breaking capacity and energy-limiting Class 3 design protect against heavy fault currents, while silver-alloy contacts and multiple arc-quenching plates extend product life. User-friendly installation on standard DIN rails and intuitive ON/OFF windows minimize downtime. Whether you’re an electrician or an end-user, this MCB delivers peace of mind through solid safety and longevity.
Ideal For
Residential electrical panels
Commercial building distribution boards
Light-industrial machinery protection
Solar PV array protection
Data centers & IT racks
As an Authorized Channel Partner of ABB and Eaton, Shansen Enterprises ensures 100% customer satisfaction. Message us on WhatsApp for your tailored quote—experience seamless ordering, expert support, and prompt delivery every time.

| Brand & Series | Eaton PLSI MCB |
|---|---|
| Model | PLSI-C25/3-GI |
| Internal Part No. | EIN-810160 |
| Poles | 3P |
| Rated Current | 25 A |
| Trip Curve | C-curve (5–10× In) |
| Breaking Capacity (Icu) | 10 kA |
| Service Breaking (Ics) | 7.5 kA |
| Rated Operational Voltage (Ue) | 240/415 V AC |
| Rated Insulation Voltage (Ui) | 660 V |
| Rated Impulse Withstand (Uimp) | 4 kV |
| Frequency | 50 Hz |
| Standards & Markings | IS/IEC 60898-1, EN/IEC 60898-1 |
| Mechanical Durability | 10 000 operations |
| Electrical Durability | 4 000 operations |
| Housing | Fire-retardant engineering plastic |
| Width | 17.5 mm/pole |
| Mounting | 35 mm DIN-rail, 2-pos clamp |
| Country of Origin | India |