📞 WhatsApp: +91 94426-33195
Email: info@shansen.in

Eaton PLSI C20/2 Miniature Circuit Breaker

0.00

Discover the Eaton PLSI C20/2 Miniature Circuit Breaker (Part No. EIN-810151), a 2-pole, 20 A protection device made for the Indian market. Its compact 35 mm module snaps onto standard DIN rails for quick installation. Engineered with a C-curve magnetic trip and 10 kA breaking capacity, it delivers fast, reliable overload and short-circuit interruption. Safety-first features include a red/green contact-position indicator, silver-alloy contacts with arc-chutes, and fire-retardant plastics. Compliant with IS/IEC 60898-1 and EN/IEC 60898-1, it thrives in –5 °C to 40 °C and up to 95 % RH environments.

Key Features at a Glance

  • 2-Pole, 20 A C-Curve breaker

  • Best-in-class 10 kA breaking capacity

  • True red/green contact-position indicator

  • Anti-weld silver-alloy contacts with 13-plate arc-chutes

  • Fire-retardant engineering plastics (UL94 V-0)

  • Energy-Limiting Class 3 for superior selectivity

  • Snap-on 35 mm DIN-rail mount (2-position clamp)

  • ISI & CE marked, IS/IEC 60898-1 & EN/IEC 60898-1 compliant

Why Choose This Product
The Eaton PLSI C20/2 combines global-grade safety and performance with a “Made for India” price point. Its robust 10 kA fault-interruption capacity and energy-limiting design minimize downstream damage, while true contact indication and fire-retardant materials heighten onsite safety. With durable silver-alloy contacts and UL-rated plastics, this MCB ensures long life and reliable operation across demanding residential and commercial environments.

Ideal For

  • Residential distribution boards

  • Commercial and retail outlets

  • Light-industrial control panels

  • Motor control circuits

  • Lighting and receptacle branches

Partner with Shansen Enterprises—your Authorized Channel Partner—to secure genuine Eaton products backed by our 100% customer satisfaction record. For the best pricing, technical support, and quick delivery, just click below to connect with us on WhatsApp and get your quote today.

Frequently Asked Questions

  1. What does “10 kA breaking capacity” mean?
    It indicates the MCB can safely interrupt fault currents up to 10 000 A without damage.

  2. How do I install the PLSI C20/2?
    Simply snap it onto a standard 35 mm DIN rail and tighten the M5 combi-head screws to 2 N·m.

  3. What is a C-curve trip characteristic?
    A C-curve MCB trips between 5× and 10× its rated current, ideal for general-purpose loads with moderate inrush currents.

Description

Electrical engineer in a green uniform and white safety helmet inspects a distribution panel in a brightly lit retail outlet, with an Eaton PLSI C20/2 20 A miniature circuit breaker, its packaging, and hand tools arranged on a wooden workbench

Additional information

Brand

Eaton

Series

PLSI Range

Model

PLSI C20/2-GI

Part Number

EIN-810151

Poles

2-Pole

Rated Current

20 A

Trip Curve

C-Curve (magnetic trip at 5–10× In)

Breaking Capacity

10 kA

Standards Compliance

IS/IEC 60898-1, EN/IEC 60898-1

Operating Temperature Range

–5 °C to 40 °C

Relative Humidity

Up to 95 % RH (non-condensing)

Mechanical Durability

10 000 operations

Electrical Durability

4 000 operations

Module Width

35 mm (2 poles)

Mounting

Snap-on 35 mm DIN rail

Country of Origin

India

Datasheet Available

Available against request