The ABB Miniature Circuit Breaker SB204M-4P 16A C is designed to provide superior protection to electrical circuits in residential, commercial, and industrial applications. Featuring a current-limiting function, this MCB offers both delayed thermal tripping for overload protection and electromechanic tripping for short circuits, ensuring high safety and reliability.
✔ 4-Pole Configuration – Provides comprehensive phase and neutral protection.
✔ Breaking Capacity – Up to 10 kA at 240/415V AC, making it ideal for various electrical setups.
✔ B, C, D Characteristics Available – Ensures the right choice for different types of loads.
✔ Compliance with IS/IEC 60898-1 – Meets international safety standards.
✔ Rated Current – 16A – Suitable for a wide range of electrical circuits.
✔ Compact System Pro M Design – Saves space while offering powerful circuit protection.
Shansen Enterprises, an Authorized Channel Partner of ABB in Coimbatore, Tamil Nadu, supplies a full range of ABB electrical products, including Contactors, Relays, RCCBs, Pilot Lights, Motor Starters, and more. With ready stock availability, we ensure a smooth supply across India with a high customer satisfaction rate.
🚀 Shipped within 48 hours via courier or transport services for quick delivery.
📲 Instant Quotes – Click on "Get Quote Via WhatsApp" on this product page and receive a fast price quote with expert assistance.
Send us a message on WhatsApp or email to get pricing and availability. We respond within 30 minutes.
| Specification | Details |
|---|---|
| ABB EcoSolutions | Yes |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 91.69% |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| Sustainable Material Content in Packaging (wt. %) | FSC 100% Paper - 43.11% FSC 100% Paper - 30.23% FSC Mix Paper - 23.68% 0% 0% |
| Extended Product Lifetime | Product Durability |
| End Of Life Disassembling Instructions | SB200M, SB200DC End of Life Instruction |
| Environmental Product Declaration - EPD | EPD SB200M MCB 10kA |
| Technical | |
| Rated Operational Current (Ie) | 16 A |
| Rated Service Short-Circuit Breaking Capacity (Ics) | 7.5 kA |
| Energy Limiting Class | 3 |
| Electrical Endurance | 20000 AC cycle |
| Mechanical Endurance | 20000 cycle |
| Number of Protected Poles | 4 |
| Number of Poles | 4P |
| Electrical | |
| Tripping Characteristic | C |
| Rated Voltage (Ur) | 415 V |
| Environmental | |
| Ambient Air Temperature | Operation -25 ... +55 °C |
| Reference Ambient Air Temperature | 30 °C |
Send us your requirements on WhatsApp or email — our team will get back to you with pricing and availability.